  g7s 2 plug-in safety relay safety relay for machine control conforms to en standard h suitable for safety circuits in press machinery, machine tools, and other production machinery h ce mark (conforms to pren50205) h positive, force-guided contacts h a minimum of 0.5 mm between contacts even when one contact is welded (pren50205 class a) h din rail-mounting and panel-mounting sockets are available note: besuretorefertothe precautions section. do not remove ordering information j safety relays number of contacts no contacts nc contacts contact form rated voltage (v) part number 6 poles 4 2 4pst-no + dpst-nc 24 vdc g7s-4a2b dc24 p 3 3 3pst-no + 3pst-nc g7s-3a3b dc24 j accessories description part number mounting sockets din-rail mounting and screw mounting p7s-14f g solder terminals p7s-14a pcb terminals p7s-14p socket mounting plate for solder terminal so ckets, holds 10 sockets P7S-A10 relay removal tool removes relay from sockets p7s-b din rail mounting track 50 cm (1.64 ft) length pfp-50n g 1 m (3.28 ft) length pfp-100n spacer pfp-s end plate pfp-m
g7s 3 specifications j ratings operation coil rated voltage rated current coil resistance minimum operate voltage release voltage max. voltage power consumption 24 vdc 30 ma 800 ? 80% max. (v) 10% (v) 110% (v) approx. 0.8 w note: 1. the rated current and coil resistan ce are measured at a coil temperature of 23 c with tolerances of 15%. 2. performance characteristics are based on a coil temperature of 23 c 3. the maximum voltage is based on an ambient operating temperature of 23 c maximum. switching section (contact ratings) load type resistive load (cos =1) inductive load (cos = 0.4, l/r = 7 ms) rated load 240vac:3a,24vdc:3a 240vac:3a,24vdc:1a maximum switching voltage 250 vac, 24 vdc maximum switching current 6a maximum switching capacity (reference value) 1,440 va, 144 w min. permissible load (see note.) 5 vdc, 10 ma contact material ag + au note: the above values are based on an operating frequency of 60 operations/min. j characteristics contact resistance (see note 2.) 100 m ? max. operate time (see note 3.) 50 ms max. release time (see note 3.) 50 ms max. maximum operating frequency mechanical 18,000 operations/hr p g q y rated load 1,800 operations/hr insulation resistance 100 m ? min. (at 500 vdc) dielectric strength 2,500 vac, 50/60 hz for 1 min (1,500 vac between contacts of same polarity) vibration mechanical 10 to 55 hz, 1.5-mm double amplitude electrical 10 to 55 hz, 0.75-mm double amplitude shock mechanical 1,000 m/s 2 (approx. 100g) electrical 100 m/s 2 (approx. 10g) life expectancy mechanical 10,000,000 operations min. (at a pprox. 18,000 operations/hr) p y electrical 100,000 operations min. (at the rated l oad and approx. 1,800 operations/hr) ambient temperature operating -- 1 0 cto70 c(14 fto158 f) no icing p storage -- 2 5 cto70 c(-13 fto158 f) no icing relative humidity 35% to 85% rh ambient storage humidity 35% to 85% rh weight approx. 65 g note: 1. the values given above are initial values. 2. measurement conditions: 5 vdc, 10 ma, voltage drops. 3. measurement conditions: rated voltage operation ambient operating temperature: 23 c (73.4 f) does not include bounce time.
g7s 4 j characteristics of safety relay socket model continuous current dielectric strength insulation resistance p7s-14 j 6a 2000 vac for 1 min. between terminals 1000 m ? min. (see note.) note: measurement conditions: measurement of the same points as for the dielectric strength at 500 vdc. j approved standards vde0435 (electrical re lays); approved by vde iec255 (electrical rel ays); approved by vde pren50205 (electrical re lays); approved by vde ul508 (industrial control device) csa22.2 no.14 (industr ial control device) e n g i neer i n g d ata j electrical life expectancy (240 vac; cos =0.4, cos =1) 100 life expectancy (x10 operations) 10 1 0 1 234 56 g7s g9s switching current (a) i(current) 4 dimensions unit: mm (inch) j safety relays g7s-4a2b g7s-3a3b terminal instal lation/internal connection diagram (bottom view) g7s-4a2b cross-section of mounting holes g7s-3a3b 62 max. (2.44) 22.5 max. (0.89) 37 max. (1.46) 5min. 24 vdc 24 vdc fourteen, 1.8 dia.
g7s 5 j safety relay sockets p7s-14f din rail-mounting socket or screw mounting terminal installation/internal connection diagram (top view) 40 max. 90.5 max. (3.56) 69 max. (2.72) 47 max. 40 max. (1.57) 47 max. (1.85) cross-section of mounting holes with safety relay mounted 7.5 4 31.3 7x4=28 p7s-14a panel-mounting socket (solder terminals) 61.5 max. (2.42) 23 max. (0.91) 33 max. (1.30) 39 max. (1.54) terminal installation/internal connection diagram (bottom view) g7s-4a2b g7s-3a3b with safety relay mounted cross-section of mounting holes (0.83) (2.24)
g7s 6 p7s-14p pcb-mounting socket (pcb terminals) terminal installation/internal connection diagram (bottom view) g7s-4a2b cross-section of mounting holes g7s-3a3b 23 max. 61.5 max. (2.42) 23 max. (0.91) 29 max. (1.14) with safety relay mounted 28 max. (1.10) two, 6.5 dia x 7.9 deep fourteen, 1.8 dia. two, 3.6 dia. 15.4 (0.61) j socket mounting plate P7S-A10 (special mounting plate for p7s-14a) p7s-b 7 59.2 (2.33) 15 (0.59) 35 (1.38) 19.3 261 max. (10.28) 81 max. (3.19) four, c0.5 1.6 (0.06) j relay removal tool
g7s 7 precautions j forcibly guided contacts when no contacts are welded, the coil will be non-energized so all nc contacts will maintain a distance between the contacts of 0.5 mm minimum. likewise if nc contacts are welded, the coil will be energized so all contacts will maintain a distance between each other of 0.5 mm minimum. caution do not touch the terminal area of the relays or the socket ter- minal area (charged area) while power is on. electric shock will result. j safety relays a safety relay is a relay with which a safety circuit can be configured. for common precautions when using and handling relays, consult omron. j contacts the coil terminals have polarity ( positive and negative).operation is not possible if these are connected in reverse. ! omron on-line global - http://www.omron.com usa - http://www.omron.com/oei canada - http://www.omron.ca all dimensions shown are in millimeters. to co nvert millimeters into inches, divide by 25.4 cat. no. gc safety-2 a printed in usa omron canada, inc. 885 milner avenue toronto, ontario m1b 5v8 416-286-6465 omron electronics llc one commerce drive schaumburg, il 60173 847-843-7900 for us technical support or other inquiries: 800-556-6766 2/03 -11/06 specifications subject to change without notice